Fire damper: advantages, disadvantages, features of product control. Fire damper bug: advantages, disadvantages, product control features Bug 1 round flange nipple

KLOP-1 valves are manufactured as a fire-retarding valve and smoke removal. Depending on the type and operating conditions, valve housings are produced different meaning fire resistance. Prevents the spread of combustion products throughout the premises of the building through, ventilation ducts and mines.
KLOP-1 valves cannot be installed in rooms of categories A and B due to fire and explosion hazard. KLOP-1 valves in explosion-proof design are installed in these premises.

Fire resistance limit of valves:

Valve KLOP-1(60)

  • in normally open (fire retardant) and normally closed modes - EI 60;
  • in smoke mode - EI 60, E 60.
Valve KLOP-1(90)
  • in normally open (fire retardant) and normally closed mode - EI 90
  • in smoke mode - EI 90, E 90.
KLOP-1 valves are produced only of the “channel” type with two flanges and external placement of the actuator. KLOP-1 round valves are also manufactured with a nipple connection.

Normally open valves KLOP-1 are manufactured in various modifications depending on the type of actuator:

  • with an electromagnetic drive in combination with a thermal lock at 72 °C (or without it);
  • round valves with an electromagnetic drive are manufactured without a thermal lock;
  • with Belimo electromechanical drives (type BF or BLF) in combination with a thermal release device at 72 °C (or without it);
  • with spring drive and thermal lock at 72 °C or 141 °C, with or without microswitches.
Smoke and normally closed dampers KLOP-1(60) and KLOP-1(90) are produced with an electromagnetic drive without a thermal lock or with Belimo reversible drives of type BLE or BE. These valves can also be equipped with Belimo electromechanical actuators with return spring type BF or BLF without TRU.

KLOP-1 valves are operational in any spatial orientation. When designing and installing valves in ventilation systems, one should take into account ease of access to the valve drive and service hatches for devices located inside the valve.

In large cross-section air ducts crossing building envelopes ventilation chambers with high-capacity fans installed in them, it is recommended to install KLOP-3 valves.

The type of climatic version of the valves is U3 according to GOST 15150-69. The valves can be installed indoors with ambient temperatures from -30 °C to +40 °C in the absence of direct exposure to precipitation and moisture condensation on the damper.

The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paint coatings and electrical insulation.

Order examples:
KLOP-1(60)-D-EM(220)-500x500-K - valve KLOP-1 with a fire resistance limit of 60 minutes, smoke, with a 220 V electromagnetic drive, with internal cross-section dimensions 500x500 mm, with a terminal block.

KLOP-1(90)-NO-MV(220)-250(Fl)-N - valve KLOP-1 with a fire resistance limit of 90 minutes, normally open (fire-retardant), with a Belimo electromechanical drive for 220 V, with an internal diameter of 200 mm, flanged, without terminal block.

Fire damper KLOP-1 on the market of domestic fire dampers is, perhaps, one of the most famous and eminent.

Its certification and the development of mass production were carried out in 1999, and the KLOP-1 valve became the first domestic certified fire damper, and the name KLOP-1 became a registered trademark. For some time, the KLOP-1 valve was the only fire damper domestic production. Well-organized marketing and work with the manufacturer design organizations made the CLOP valve popular, often found in project documentation. This probably contributed to the fact that the name KLOP-1 became a household name; you may encounter situations when a customer, applying for valves, says: “I need to buy KLOP-1,” although the specific name of the valve is not indicated in his documentation and the valve CLOP-1 can be replaced with others fire dampers with similar parameters.

The fire damper KLOP-1 is installed in the channels of general ventilation and air conditioning with mechanical draft stimulation. Fire retardant (normally open valves) prevent the spread of fire through these channels, and smoke (normally closed valves) prevent the spread or removal of smoke.

Fire damper KLOP-1 is produced in two modifications:

CLOP-1(60);

CLOP-1(90);

The difference between them lies in the fire resistance limits.

KLOP-1 (60) has a fire resistance limit of 60 minutes (1 hour).

KLOP-1 (90) has a fire resistance limit of 90 minutes (1.5 hours).

The KLOP-1 valve can perform the functions of both a fire-retarding valve (damper in the “normally open” position) and a smoke exhaust valve (damper in the “normally closed” position).

The valve body can be made of either round or rectangular (square) cross-section.

KLOP-1 is intended for installation only in the canal. The drive that transfers the valve flap from the initial state to the operating state is located outside the valve. To control the position of the damper, a special inspection hatch is provided on the valve. It is used when an air duct is connected to the valve on both sides and it is not possible to look inside the already installed valve through the flow section.

The body of the KLOP-1 valve is made of carbon (black) steel, subsequently painted. In this way, KLOP-1 differs from the KLOP-2 valve, the body of which is made of galvanized steel.

A rectangular (square) valve is equipped on both sides with flanges through which it is attached to the ventilation duct.

The round valve can be manufactured either on flanges or for nipple mounting in the ventilation duct.

Fire damper KLOP-1 is equipped with the following types actuators for controlling the valve flap:

Electromechanical drive BELIMO type BF(24), BF(220) or BLF(24), BLF(220) with return spring with supply voltage 24V or 220V;

Electromagnetic EM(220), EM(24) or EM(12) - electromagnetic drive with supply voltage 12V, 24V or 220V;

TZ - spring drive with thermal lock;

TZ(M) - spring drive with thermal lock and microswitches;

When choosing an actuator for fire dampers, you should consider that:

Part 2 Art. 138 Federal Law No. 123-FZ prohibits the use of actuators of the TZ and TZ(M) types on NO fire dampers in Russian Federation.

The use of MV type actuators on NC and smoke valves in the Russian Federation is contrary to clause 7.18 of SP 7.13130.2009.

The price of fire dampers KLOP-1, KLOP-2, KLOP-3, KOM-1, KDM-2 and KLAD-2 are given below.

The price of a fire damper with dimensions different from those indicated in the table is determined on the larger side. For example, the price of a KLOP-1 valve with dimensions 400x200 is determined as the price of a 400x400 valve. The price of a KLOP-2 valve with dimensions 600x350 is determined as the price of a valve with dimensions 600x600, etc.

To clarify the price of fire dampers, please contact the indicated telephone numbers or send a request by e-mail:

Main characteristics of the KLOP-1 valve:

Characteristic

type of drive

Electromechanical

Electromechanical

Thermal lock (fuse link + spring drive)

Solenoid with thermal lock (for round valves without thermal lock)

Fire resistance limit

60 minutes in “Normal Open” position

60 minutes in Normally Closed position

90 minutes in “Normal Open” position

90 minutes in Normally Closed position

Climatic operating conditions

Temperature environment from -30С to +40С

Relative humidity no more than 80%

Direct precipitation is not allowed

Material

Carbon steel sheet

Carbon steel sheet

Execution

Wall or channel

Wall or channel

Damper design

“Normally open” - when used as a fire-retarding valve;

“Normally closed” - when used as a fire-retardant valve;

Fire damper KLOP-1 round section

Fire damper KLOP-1 rectangular section

Fireproof normally open (fire retardant) KLOP-1 valves are designed to block the spread of fire and combustion products through air ducts, shafts and ducts of ventilation and air conditioning systems of buildings and structures for various purposes. KLOP-1 smoke and normally closed valves are used as smoke ventilation valves. The valves are used in accordance with regulatory requirements. KLOP-1 valves cannot be installed in rooms of categories A and B due to explosion and fire hazard. KLOP-1 valves in explosion-proof design are installed in these premises.

Fire resistance limit of valves:

CLOP-1 (60) -
/////// when the drive is located on the thermal side - EI 60
when the drive is located on the side opposite to the thermal influence - EI 60
when installing the valve on a section of the air duct outside the enclosing
building structure with a standardized fire resistance limit - EI 60
- in normally closed valve mode - EI 60
- in smoke valve mode - E 60
CLOP-1 (90) - in normally open (fire retardant) valve mode:
when the drive is located on the thermal side - EI 90
when the drive is located on the side opposite to the thermal influence - EI 90
when installing the valve on a section of the air duct outside the building envelope
structures with a regulated fire resistance limit - EI 90
- in normally closed valve mode - EI 90
- in smoke valve mode - E 90

KLOP-1 valves are produced only of the “channel” type with two flanges (rectangular and round valves) or with a nipple connection (circular valves). Valve drive installed externally
housings. The rectangular valve body is made of carbon cold-rolled steel and then
painted, round valve body made of galvanized steel.

Normally open (NO) valves KLOP-1 are manufactured in various modifications depending on the type of drive:
- with an electromagnetic drive in combination with a thermal lock at 72°C (on special order at 93 or 141°C);
- round valves with an electromagnetic drive are manufactured without a thermal lock;
- with BELIMO electromechanical drives (BF or BLF) in combination with a thermal release device at 72°C (on special order at 93 or 141°C);
- with a spring drive and a thermal lock at 72°C or 141°C, with or without microswitches (Part 2 of Article 138 of Federal Law No. 123-FZ prohibits the use of these drives in the Russian Federation).

Normally closed (NC), including smoke, KLOP-1 valves are produced with an electromagnetic drive without a thermal lock or reversible BELIMO drives of type BLE or BE (for large valves). On valves manufactured for foreign countries, BELIMO electromechanical actuators with a return spring type BF or
BLF without TRU (the use of electromechanical drives on smoke ventilation valves in the Russian Federation is contrary to SP 7.13130).

Design diagrams for KLOP-1 valves

With BELIMO drive With electromagnetic drive With spring drive and TK

1– valve body; 2 – damper; 3 – protective casing; 4 – drive; 5 – thermal lock; 6– inspection hatch; 7 – key; 8 – flap retainer ring; 9 – TRU; 10 - terminal block; 11– damper position indicator; 12– key socket for manually charging the drive spring; 13– lever for manual actuation of the damper drive

L 1 =120 mm – length of the valve body from the flange to the edge of the protective casing.
In valves with dimensions A< 600 мм используется шина №20(А
1 =A+40 mm, B 1 =B+40 mm).
In valves with dimensions A ≥ 600 mm, tire No. 30 is used (A
1 =A+60 mm, B 1 =B+60 mm).

At A<600 мм один смотровой люк располагается в центребоковой поверхности клапана слева (вид со стороны привода),а при А ≥ 600 мм – один люк в верхней части боковойповерхности справа (см. рис.) и второй люк в нижней частипротивоположной поверхности справа.
On valves with electromechanical drive BELIMO prV< 400 мм ТРУ устанавливается на крышке люка клапана, апри В  400 мм – на корпусе рядом с приводом.

KLOP-1 valves are operational in any spatial orientation. When designing and installing valves
in ventilation systems, ease of access to the valve drive and service hatches for devices located inside the valve should be taken into account. In large cross-section air ducts crossing the enclosing structures of ventilation chambers with high-capacity fans installed in them, it is recommended to install KLOP-3 valves.

Type of climatic version of valves:
– U3 according to GOST 15150-69. The valves can be installed indoors with ambient temperatures from -30 °C to +40 °C in the absence of direct exposure to precipitation and moisture condensation on the damper. The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paint and varnish coatings and electrical insulation.

Designation structure for conventional KLOP-1 valves when ordering and in the documentation

BUG-1 - (...) - ... - ...x... - ... - ...
Valve name
Fire resistance limit, min (60 or 90)
Functional purpose:
BUT - normally open
NC - normally closed
D - smoke
Valve internal cross-section dimensions
AxB, mm - rectangular
D(Np), mm - round nipple
D(Fl), mm - round flange
Damper drive type:
EM(220), EM(24) or EM(12) - electromagnetic
MB(220) or MB(24) - BELIMO electromechanical actuator type BF or BLF with spring return
MBE(220) or MBE(24) - BELIMO reversible drive type BE or BLE (in parentheses - drive supply voltage, V)
TZ - spring drive with thermal lock
TZ(M) - spring drive with thermal lock and microswitch
Availability of junction box with terminal block
K - yes
N - no

Note.

1.Part 2 art. 138 of Federal Law No. 123-FZ prohibits the use of actuators of the TZ and TZ(M) types on NO fire dampers in the Russian Federation. The use of MV type actuators on NC and smoke valves in the Russian Federation is contrary to SP 7.13130 ​​( ) .
2. When ordering NO valves with EM or MV actuators, a temperature-sensitive element (TZ - for an EM actuator at 72°C, TRU - for a MV actuator at 72°C) is included in the drive, with the exception of round valves with an EM actuator.
3. When ordering valves for special purposes, the design option is additionally indicated.

Valve overhang values ​​for a rectangular valve body

B, mm 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
X, mm 0 0 22 47 72 97 122 147 172 197 222 247 272 297 322 347 372 397
X1, mm 0 0 0 0 0 0 0 0 12 37 62 87 112 137 162 187 212 237
X – flap overhang at the valve inlet, mm; X1 – flap overhang at the valve outlet, mm

FIRE VALVES BUG 1

The valves are certified by VNIIPO EMERCOM of Russia and the Center for Explosion-Proof and Mining Electrical Equipment.

Purpose

Fire-prevention normally open (fire-retarding) valves KLOP-1 are designed to block the spread of fire and combustion products through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes.

Normally closed (including smoke) valves KLOP-1 are used as smoke ventilation valves. The valves are used in accordance with regulatory requirements. KLOP®-1 valves cannot be installed in rooms of categories A and B due to fire and explosion hazard. In these premises, explosion-proof valves KLOP-1V are installed.

Fire resistance limit of valves

KLOP-1(60) - in the mode of a normally open (fire-retarding) valve:
when the drive is located on the thermal side - EI 60;
when the drive is located on the side opposite to the thermal effect - EI 60;
when installing the valve on a section of the air duct outside the building envelope with a rated fire resistance limit of EI 60;
in normally closed valve mode - EI 60;
in smoke valve mode - E 60.

KLOP-1(90) - in the mode of a normally open (fire-retarding) valve:
when the drive is located on the thermal side - EI 90;
when the drive is located on the side opposite to the thermal effect - EI 90;
when installing the valve on a section of the air duct outside the building envelope
structures with a standardized fire resistance limit - EI 90;
in normally closed valve mode - EI 90;
in smoke valve mode - E 90.

KLOP-1 valves are produced only of the “channel” type with two flanges (rectangular and round valves) or with a nipple connection (circular valves). The valve drive is installed outside the housing. The body of rectangular valves is made of carbon cold-rolled steel with subsequent painting, the body of round valves is made of galvanized steel.

Normally open (NO) valves KLOP-1 are manufactured in various modifications depending on the type of drive: - with an electromagnetic drive in combination with a thermal lock at 72 ° C (on special order for 93 or 141 ° C); - round valves with an electromagnetic drive are manufactured without thermal lock; - with BELIMO electromechanical drives (BF or BLF) in combination with a thermal release device at 72°C (on special order at 93 or 141°C);

Cassette made of NO valves KLOP-1 with
electromagnetic drive (version 1)

Cassette made of NO valves KLOP-1
with electromagnetic drive (version 2)

Attention!

Our company supplies products from several manufacturing plants with a similar range. The manufacturer reserves the right to make changes to the design and model range of supplied equipment. If necessary, you can request more detailed information on a specific model from our managers.

  • Fire-prevention normally open (fire-retarding) valves KLOP-1 are designed to block the spread of fire and combustion products through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes.
  • KLOP-1 smoke and normally closed (NC) valves are used as smoke ventilation valves. The valves are used in accordance with regulatory requirements.
  • KLOP-1 valves cannot be installed in rooms of categories A and B due to fire and explosion hazard. In these premises, explosion-proof valves KLOP-1V or KLOP-2V are installed.
  • KLOP-1 valves are operational in any spatial orientation. When designing and installing valves in ventilation systems, one should take into account ease of access to the valve drive and service hatches for devices located inside the valve.
  • KLOP-1 valves are produced only of the “channel” type with two flanges (rectangular and round valves) or with a nipple connection (circular valves). The valve actuator is installed outside the housing. The body of rectangular valves is made of carbon cold-rolled steel with subsequent painting, the body of round valves is made of galvanized steel.

Valve fire resistance limit

Fire resistance limit of KLOP-1(60/90) valves in normally open (fire-retarding) valve mode:

  • when the drive is located on the thermal side - EI 60/90;
  • when the drive is located on the side opposite to the thermal influence - EI 60/90;
  • when installing the valve on a section of the air duct outside the building envelope with a rated fire resistance limit - EI 60/90;
  • in normally closed valve mode - EI 60/90;
  • in smoke valve mode - EI 60/90.

Modifications of fire-retarding valves KLOP-1 depending on the type of actuator:

  • with an electromagnetic drive in combination with a thermal lock at 72 °C (on special order at 93 or 141 °C);
  • round valves with an electromagnetic drive are manufactured without a thermal lock;
  • with BELIMO electromechanical drives (type BF or BLF) in combination with a thermal release device (TRD) at 72 °C (on special order at 93 or 141 °C);
  • with a spring drive and a thermal lock at 72 °C or 141 °C, with or without microswitches (Part 2 of Article 138 of Federal Law No. 123-FZ prohibits the use of these drives in the Russian Federation).

Modifications of smoke and normally closed (NC) valves KLOP-1 (60) and KLOP-1 (90):

  • with electromagnetic actuator without thermal lock or reversible BELIMO actuators type BLE or BE for large valve sizes

terms of Use

Type of climatic modification of valves is U3 in accordance with GOST 15150. The valves can be installed indoors with an ambient temperature from - 30 °C to + 40 °C in the absence of direct exposure to precipitation and moisture condensation on the damper. The environment must be explosion-proof and free of aggressive vapors and gases in concentrations that destroy metals, paint and varnish coatings and electrical insulation.

SPECIAL PURPOSE VALVES

Valves for maritime climates and damp areas

  • Valves for areas with a maritime climate are made of stainless steel. The electromechanical or reversible BELIMO actuator is housed in an enclosure with a protection degree of IP 66. The valve body is made of rectangular cross-section. Type of climatic modification - M2 according to GOST 15150-90.
  • Normally open valves with an electromechanical drive are manufactured without hydraulic valves (including explosion-proof valves).
  • The fire resistance limit of the valve is A 60 (60 min).

Characteristics of the external environment during valve operation

  • maximum operating values ​​of ambient air temperature: upper value - plus 40 °C, lower - minus 30 °C in the absence of direct exposure to precipitation and moisture condensation on the damper.
  • The average monthly relative humidity in the warmest and most humid period is 70% at 22 °C;
  • the upper value of relative air humidity is 98% at 25 °C;
  • atmosphere type - III according to GOST 15150-90.

The valves have passed the tests for compliance with the requirements for valves for exposure to salt fog, splash resistance and dust resistance, based on the results of which a corresponding conclusion was obtained. The valves have a certificate of type approval from the Russian Maritime Register of Shipping and a certificate of approval from the Russian River Register, which allows them to be used both on sea vessels and stationary offshore platforms, and on river vessels. These valves can be installed in rooms with high humidity.

Transport valves

  • The valves have design features that take into account the specific operating conditions at transport facilities and can be used in ventilation and air conditioning systems for railway rolling stock.
  • The valves have been tested for vibration and impact resistance.

Valves for rooms with increased requirements for cleanliness of the working environment

  • Valves are manufactured in rectangular and round sections. Round valves with a diameter of up to 315 mm are manufactured in flange and nipple versions, with a diameter of more than 315 mm - only in nipple version. Special purpose stainless steel is used in the manufacture of the valve body, damper and casing. The valves are used in the pharmaceutical, microelectronics industries, etc.
  • The main technical characteristics of special-purpose valves are similar to the characteristics of KLOP-1 valves of conventional (general industrial) design with rectangular and circular sections.
  • The main technical characteristics of special-purpose valves are similar to the characteristics of KLOP-1 valves with rectangular and circular sections.
 
Articles By topic:
Volynians main city.  Reasons for the name.  Tribes of the forest zone of the Dnieper right bank
United the Volynians, Drevlyans, Polyans and Dregovichi in the so-called. “Duleb group”, which represented the southwestern branch of the Eastern Slavs. A similar point of view was held by I. P. Rusanova, G. N. Matyushin, as well as V. V. Boguslavsky and E. I. Kuksina. Others
Pickled grapes: best recipes
Pickled grapes are a wonderful dessert that can be prepared for the winter at home. There are many options for preparing berries, but several simple recipes are especially popular.
Pickled grapes are a wonderful dessert.
What does a new blue towel mean in a dream?
Find out from the online dream book what the Towel is for in a dream by reading the answer below as interpreted by the interpretive authors.
What does a towel mean in a dream? Dream Interpretation of the 21st Century Why do you dream about a Towel and what does it mean: Towel - Drying yourself with a towel in a dream is a sign that