Fire bug valve 1. Fire bug valve: advantages, disadvantages, product control features. Valves for maritime and wet areas
Fire damper KLOP-1 in the market of domestic fire dampers is perhaps one of the most famous and eminent.
Its certification and development of mass production was carried out in 1999, and the KLOP-1 valve became the first domestic certified fire damper, and the name KLOP-1 became a registered trademark. For some time, the Klop-1 valve was the only fire damper domestic production. Well-organized manufacturer marketing and work with design organizations made the KLP valve popular, often found in project documentation. Probably, this contributed to the fact that the name KLP-1 has become a household name, you may encounter such situations when the customer, when applying for valves, says: "I need to buy KLP-1", although the specific name of the valve is not indicated in his documentation and the valve KLP-1 can be replaced by other fire dampers with similar parameters.
The fire damper KLOP-1 is installed in the channels of general ventilation and air conditioning with mechanical draft induction. Fire-retarding (normally open valves) prevent the spread of fire through these channels, and smoke (normally closed valves) prevent the spread or removal of smoke.
The fire damper KLOP-1 is produced in the form of two modifications:
Klop-1(60);
Klop-1(90);
The difference between them lies in the limits of fire resistance.
Klop-1 (60) has a fire resistance limit of 60 minutes (1 hour).
Klop-1 (90) has a fire resistance limit of 90 minutes (1.5 hours).
The KLOP-1 damper can perform the functions of both a fire damper (damper in the "normally open" position) and a smoke exhaust valve - (damper in the "normally closed" position).
The valve body can be made both round and rectangular (square) section.
Klop-1 is intended for installation only in the channel. The drive that transfers the damper flap from the initial state to the working state is located outside the damper. To control the position of the damper, a special inspection hatch is provided on the valve. It is used when an air duct is connected to the valve on both sides and it is not possible to look inside the already installed valve through the flow area.
The body of the KLOP-1 valve is made of carbon (black) steel, subsequently painted. This KLOP-1 differs from the valve KLOP-2, the body of which is made of galvanized steel.
The damper of rectangular (square) section is equipped on both sides with flanges through which it is attached to the ventilation duct.
The round section damper can be made both on flanges and for nipple mounting in the ventilation duct.
Fire damper KLOP-1 is completed the following types actuators for damper flap control:
Electromechanical actuator BELIMO type BF(24), BF(220) or BLF(24), BLF(220) with a return spring with a supply voltage of 24V or 220V;
Electromagnetic EM (220), EM (24) or EM (12) - electromagnetic drive with a supply voltage of 12V, 24V or 220V;
ТЗ - spring drive with thermal lock;
ТЗ(М) - spring drive with thermal lock and microswitches;
When choosing an actuator for fire dampers, consider that:
Part 2 Art. 138 federal law No. 123-FZ prohibits the use of TZ and TZ(M) type actuators on NO fire dampers in Russian Federation.
The use of MV type actuators for NC and smoke dampers in the Russian Federation is contrary to clause 7.18 of SP 7.13130.2009.
The price of fire dampers KLOP-1, KLOP-2, KLOP-3, KOM-1, KDM-2 and KLAD-2 are given below.
The price of a fire damper with dimensions other than those indicated in the table is determined by the larger side. For example, the price of a KLOP-1 valve with dimensions of 400x200 is determined as the price of a 400x400 valve. The price of a KLOP-2 valve with dimensions of 600x350 is determined as the price of a valve with dimensions of 600x600, etc.
To clarify the price of fire dampers, please call the indicated phones or send a request by e-mail:
The main characteristics of the valve KLOP-1:
Characteristic |
||
type of drive |
Electromechanical |
Electromechanical Thermal lock (fusible link + spring drive) Solenoid with thermal lock (for round valves without thermal lock) |
Fire resistance limit |
60 minutes in Normally Open position 60 minutes in Normally Closed position |
90 minutes in Normally Open position 90 minutes in Normally Closed position |
Climatic operating conditions |
Ambient temperature from -30С to +40С Relative humidity no more than 80% Direct precipitation is not allowed |
|
Material |
Carbon steel sheet |
Carbon steel sheet |
Execution |
Wall or channel |
Wall or channel |
Damper design |
"Normally open" - when used as a fire-retardant damper; "Normally closed" - when used as a fire-retardant damper; |
Fire damper KLOP-1 of round section
Fire damper KLOP-1 rectangular section
- Fire-fighting normally open (fire-retarding) dampers KLOP-1 are designed to block the spread of fire and combustion products through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes.
- KLOP-1 smoke dampers and normally closed (NC) dampers are used as smoke ventilation dampers. Valves are used in accordance with regulatory requirements.
- KLOP-1 dampers are not subject to installation in rooms of categories A and B in terms of fire and explosion hazard. In these rooms, KLOP-1V or KLOP-2V dampers are installed in an explosion-proof design.
- KLOP-1 dampers are operable in any spatial orientation. When designing and installing valves in ventilation systems, one should take into account the convenience of access to the valve actuator and service hatches for devices inside the valve.
- KLOP-1 dampers are produced only in the "duct" type with two flanges (rectangular and round valves) or with a nipple connection (round valves). The valve actuator is installed outside the body. Rectangular valve body is made of cold-rolled carbon steel with subsequent painting, round valve body is made of galvanized steel.
Valve fire rating
Fire resistance limit of valves KLOP-1 (60/90) in the mode of a normally open (fire-retarding) valve:
- when the drive is located on the side of thermal influence - EI 60/90;
- when the drive is located on the side opposite to the thermal effect - EI 60/90;
- when installing the damper on the duct section outside the enclosing building structure with a standardized fire resistance limit - EI 60/90;
- in the normally closed valve mode - EI 60/90;
- in smoke valve mode - EI 60/90.
Modifications of fire-retarding dampers KLOP-1 depending on the type of drive:
- with electromagnetic drive in combination with a thermal lock at 72 °C (by special order at 93 or 141 °C);
- round valves with electromagnetic drive are manufactured without thermal lock;
- with BELIMO electromechanical actuators (type BF or BLF) in combination with a thermal disconnection device (TRU) at 72 °C (by special order at 93 or 141 °C);
- with a spring drive and a thermal lock at 72 °C or 141 °C, with or without microswitches (Part 2 of Article 138 of Federal Law No. 123-FZ prohibits the use of these drives in the Russian Federation).
Modifications of flue and normally closed (NC) valves KLOP-1 (60) and KLOP-1 (90):
- with solenoid actuator without thermal lock or BELIMO reversing actuators type BLE or BE for valves large sizes
terms of Use
Type of climatic version of dampers U3 according to GOST 15150. The dampers can be installed indoors with an ambient temperature from -30 °C to +40 °C in the absence of direct exposure to atmospheric precipitation and moisture condensation on the damper Environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paint coatings and electrical insulation.
VALVES FOR SPECIAL PURPOSE
Valves for maritime and wet areas
- Valves for areas with a maritime climate are made of stainless steel. The BELIMO electromechanical or reversible actuator is placed in a shell with a degree of protection IP 66. The valve body is made of a rectangular section. Type of climatic modification - M2 in accordance with GOST 15150-90.
- Normally open valves with an electromechanical drive are manufactured without GWS (including explosion-proof valves).
- The fire resistance limit of the valve is A 60 (60 min).
Characteristics external environment during valve operation
- limit operating values of ambient air temperature: upper value - plus 40 °C, lower value - minus 30 °C in the absence of direct exposure to precipitation and moisture condensation on the damper.
- The average monthly value of relative air humidity in the warmest and most humid period is 70% at 22 °С;
- upper value of relative air humidity - 98% at 25 °С;
- atmosphere type - III according to GOST 15150-90.
The dampers have passed the salt spray, splash and dust tightness test, which resulted in an appropriate conclusion. The valves have a type approval certificate from the Russian Maritime Register of Shipping and a certificate of approval from the Russian River Register, which allows them to be used both on sea vessels and fixed offshore platforms, and on river vessels. These valves can be installed in rooms with high humidity.
Valves "transport" execution
- The valves have design features that take into account the specifics of operating conditions at transport facilities, and can be used in ventilation and air conditioning systems of railway rolling stock.
- The valves have been tested for vibration resistance and impact.
Valves for rooms with increased requirements for the cleanliness of the working environment
- Valves are made of rectangular and round section. Round valves with a diameter of up to 315 mm are manufactured in flanged and nipple design, with a diameter of more than 315 mm - only in nipple design. In the manufacture of the valve body, damper and casing, stainless steel special purpose. Valves are used in the pharmaceutical, microelectronic industries, etc.
- Main specifications valves for special purposes are similar to the characteristics of KLP-1 valves of conventional (general industrial) execution of rectangular and round sections.
- The main technical characteristics of special purpose dampers are similar to those of KLOP-1 dampers of rectangular and round sections.
KLOP-1 valves are manufactured as a fire damper and smoke exhaust. Depending on the type and operating conditions of the valve premises, various meanings fire resistance. They prevent the spread of combustion products through the premises of the building through, ventilation ducts and mines.
KLOP-1 dampers are not subject to installation in rooms of categories A and B in terms of fire and explosion hazard. In these rooms, KLOP-1 dampers are installed in an explosion-proof design.
Fire resistance limit of valves:
Valve KLOP-1(60)
- in the mode of normally open (fire-retardant) and normally closed - EI 60;
- in smoke mode - EI 60, E 60.
- in the mode of normally open (fire-retardant) and normally closed - EI 90
- in smoke mode - EI 90, E 90.
Normally open valves KLOP-1 are manufactured in various modifications depending on the type of drive:
- with electromagnetic drive in combination with a 72 °C thermal lock (or without it);
- round valves with electromagnetic drive are manufactured without thermal lock;
- with Belimo electromechanical actuators (type BF or BLF) in combination with (or without) a 72 °C thermal cut-out device;
- with spring drive and thermal lock at 72°C or 141°C, with or without microswitches.
KLOP-1 dampers are operable in any spatial orientation. When designing and installing valves in ventilation systems, one should take into account the convenience of access to the valve actuator and service hatches for devices inside the valve.
In large-section air ducts crossing the building envelope ventilation chambers with high-performance fans installed in them, it is recommended to install KLOP-3 dampers.
Type of climatic modification of valves - U3 in accordance with GOST 15150-69. The dampers can be installed indoors with an ambient temperature of -30 °C to +40 °C in the absence of direct exposure to atmospheric precipitation and moisture condensation on the damper.
The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paintwork and electrical insulation.
Order examples:
KLOP-1(60)-D-EM(220)-500x500-K - damper KLOP-1 with a fire resistance of 60 minutes, smoke, with an electromagnetic drive for 220 V, with an internal section of 500x500 mm, with a terminal block.
KLOP-1(90)-NO-MV(220)-250(Fl)-N - damper KLOP-1 with a fire resistance limit of 90 minutes, normally open (fire-retardant), with a Belimo electromechanical drive for 220 V, with an internal cross-section diameter of 200 mm, flanged, without terminal block.
Fire-fighting normally open (fire-retarding) dampers KLP ® -1 are designed to block the spread of fire and combustion products through air ducts, shafts and channels of ventilation and air conditioning systems of buildings and structures for various purposes. Normally closed (including smoke) dampers KLOP ® -1 are used as dampers for smoke ventilation. The use of valves is carried out in accordance with regulatory requirements. KLOP ® -1 dampers are not subject to installation in rooms of categories A and B in terms of explosion and fire hazard.
Fire resistance limit of valves:
KLOP ® -1 (60) - in the mode of normally open (fire-retardant) and normally closed - EI 60;
in smoke mode - EI 60, E 60.
KLOP ® -1 (90) - in the mode of normally open (fire-retardant) and normally closed - EI 90;
in smoke mode - EI 90, E 90.
KLOP ® -1 dampers are produced only in “channel” type with two flanges (rectangular and round valves) or with nipple connection (round valves). The valve actuator is installed outside the housing. Rectangular valve body is made of cold-rolled carbon steel with subsequent painting, round valve body is made of galvanized steel.
Normally open (NO) valves KLOP ® -1 are manufactured in various modifications depending on the type of drive:
- with electromagnetic drive in combination with a 72°C thermal lock (or without it);
- round valves with electromagnetic drive are manufactured without thermal lock;
- with BELIMO electromechanical actuators (BF or BLF) in combination with (or without) a 72°C thermal cut-out device;
- with spring drive and thermal lock at 72°C or 141°C, with or without microswitches.
Normally closed (NC), including smoke dampers KLOP ® -1(60) KLOP ® -1(90) are produced with an electromagnetic actuator without a thermal lock or BELIMO reversible actuators of the BLE or BE type (for large valves). On valves manufactured for foreign countries, electromechanical actuators BELIMO with a return spring type BF or BLF without TRU can also be installed.
KLOP ® -1 dampers are operable in any spatial orientation.
When designing and installing valves in ventilation systems, the convenience of access to the valve actuator and inspection hatches in its body should be taken into account. In air ducts of large cross section, crossing the enclosing structures of ventilation chambers with high-capacity fans installed in them, it is recommended to install KLOP ® -3 dampers.
Type of climatic modification of valves - U3 in accordance with GOST 15150-69. The dampers can be installed indoors with an ambient temperature of -30°C to +40°C in the absence of direct exposure to atmospheric precipitation and moisture condensation on the damper. The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paintwork and electrical insulation.
Design schemes KLOP ® -1
1 - valve body; 2 - damper; 3 - protective cover; 4 - drive; 5 - thermal lock; 6 - inspection hatch; 7 - key; 8 - damper retainer ring; 9 - TRU; 10 - terminal block; 11 - damper position indicator; 12 - key socket for manual cocking of the drive spring; 13 - lever for manual actuation of the damper drive
L1=120 mm is the length of the valve body from the flange to the edge of the protective casing.
In valves with dimensions, A< 600 мм используется шина № 20 (А1=А+40 мм, B1=B+40 мм).
Valves with dimensions A ≥600 mm use busbar No. 30 (A1=A+60 mm, B1=B+60 mm).
At, A<600 мм один смотровой люк располагается в центре боковой поверхности клапана слева (вид со стороны привода),
and when, A≥600 mm - one hatch in the upper part of the side surface on the right (see Fig.) and the second hatch in the lower part of the opposite surface on the right.
On valves with electromechanical actuator BELIMO at V< 400 мм ТРУ устанавливается на крышке люка клапана, а при В ≥400 мм — на корпусе рядом с приводом.
The area of the passage section of the KLOP ® -1 valves of rectangular section is determined by the formula:
Fcl \u003d (A - 36) (B - 63) / 10 6, m 2
where, A, B are the internal dimensions of the cross section of the damper (air duct), mm, (A≥B).
Values of damper projections for the valve body of rectangular section
B, mm | 150 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 550 | 600 | 650 | 700 | 750 | 800 | 850 | 900 | 950 | 1000 |
X, mm | 0 | 0 | 22 | 47 | 72 | 97 | 122 | 147 | 172 | 197 | 222 | 247 | 272 | 297 | 322 | 347 | 372 | 397 |
X1, mm | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 37 | 62 | 87 | 112 | 137 | 162 | 187 | 212 | 237 |
Х — damper projection at the valve inlet, mm; X1 - flap projection at the outlet of the valve, mm
Installation schemes for KLOP ® -1 valves are presented on pages 68, 69.
To compensate for the length of the damper projection (for example, when installing a decorative grille on a flange or when installing a damper in a building structure with a thickness of more than L1, additional duct sections of the appropriate length can be made.
Cassette schemes
Version 1 (welded)
9 - self-tapping screw.
Fk \u003d (Ak - 126) (Bk - 36) / 10 6, m 2
Execution 2.1 (Вк≤300 mm, welded)
1 - body; 2 - damper; 3 - protective cover; 4 - drive; 5 - inspection hatch; 6 - TRU (for NO valves); 7 - junction box with terminal block; 8 - bar;
9 - self-tapping screw.
Fk \u003d (Ak - 72) (Bk - 63) / 10 6, m 2
Ak, Bk - dimensions of the internal section of the cassette (air duct), mm
Fк - area of the passage section of the cassette, m 2
Execution 2.2 (Вк > 300 mm, on slats)
1 - body; 2 - damper; 3 - protective cover; 4 - drive; 5 - inspection hatch; 6 - TRU (for NO valves); 7 - junction box with terminal block; 8 - bar;
9 - self-tapping screw.
Fk \u003d (Ak - 132) (Bk - 63) / 10 6, m 2
Ak, Bk - dimensions of the internal section of the cassette (air duct), mm
Fк - area of the passage section of the cassette, m 2
Round valves
Valves are made of galvanized steel.
Design schemes KLOP ® -1 round section
With BELIMO drive | With electromagnetic drive | With spring drive and TK |
for flanged valve L=350mm, Lo=93mm, L1=120mm; For nipple valve L=450mm, Lo=143mm, L1=175mm L1 - valve body length up to edges of the protective cover, mm | 1 - valve body 2 - damper 3 - protective cover 4 - drive 5 - inspection hatch 6 - key 7 - TRU | 8 - damper retainer ring 9 - thermal lock 10 - damper position indicator 11 - key socket for manual cocking the drive spring 12 - manual actuation lever damper actuator |
Values for damper projections outside the valve body
D, mm | 160 | 180 | 200 | 225 | 250 | 280 | 315 | 355 | 400 | 450 | 500 | 560 | 630 | 710 | 800 |
with flange connection | |||||||||||||||
X, mm | 0 | 0 | 7 | 19 | 32 | 47 | 64 | 85 | 107 | 132 | 157 | 187 | 222 | 262 | 307 |
X1, mm | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 51 | 91 | 136 |
with nipple connection | |||||||||||||||
X, mm | 0 | 0 | 0 | 0 | 0 | 0 | 14 | 35 | 57 | 82 | 107 | 137 | 172 | 212 | 257 |
X1, mm | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 41 | 86 |
By special order, valves with a diameter of 900 and 1000 mm with a BELIMO actuator can be manufactured.
Standard size range of KLOP ® -1 dampers of circular cross section and junctions, local resistance coefficients of dampers zB and dampers with two junctions zB * and the flow area of dampers Fkl depending on the diameter of the internal section of the air duct D.
Flanged and nipple valves with a diameter of 160 and 180 mm are manufactured only with an electromagnetic actuator or a BELIMO actuator.
For installation in air ducts with a diameter of 100 and 125 mm, flanged dampers with a diameter of 160 or 200 mm are manufactured with tubular or plate transitions.
For installation in air ducts with a diameter of 140 mm, flanged dampers with a diameter of 160 mm with tubular transitions or flanged dampers with a diameter of 200 mm with plate transitions are manufactured.
Weight of KLOP ® -1 valves, kg
D, mm | 160 | 180 | 200 | 225 | 250 | 280 | 315 | 355 | 400 | 450 | 500 | 560 | 630 | 710 | 800 |
flanged | |||||||||||||||
TK | - | - | 5,0 | 5,6 | 6,2 | 6,8 | 7,7 | 10,2 | 11,8 | 13,5 | 15,7 | 18,3 | 21,5 | 26,0 | 29,4 |
BELIMO | 6,1 | 6,8 | 7,6 | 8,2 | 8,8 | 9,5 | 10,5 | 13,0 | 14,5 | 16,2 | 18,4 | 21,0 | 24,2 | 28,7 | 32,9 |
EM | 6,3 | 7,0 | 7,8 | 8,3 | 9,0 | 9,7 | 10,6 | 13,2 | 14,7 | 16,4 | 18,6 | 21,2 | 24,5 | 28,9 | 33,1 |
nipple | |||||||||||||||
TK | 3,9 | 4,1 | 4,3 | 4,5 | 5,0 | 5,4 | 6,2 | 8,5 | 9,8 | 11,3 | 13,3 | 15,6 | 18,5 | 25,3 | 29,5 |
BELIMO | 4,8 | 5,0 | 5,2 | 5,6 | 6,1 | 6,6 | 7,5 | 9,8 | 11,1 | 12,5 | 14,6 | 16,8 | 21,2 | 28,8 | 33,1 |
EM | 6,1 | 6,4 | 6,7 | 7,1 | 7,7 | 8,2 | 9,0 | 11,4 | 12,6 | 14,1 | 16,1 | 18,4 | 21,4 | 28,9 | 33,3 |
Fire-fighting normally open dampers KLOP-1 designed to block the spread of fire and combustion products. Normally closed valves KLOP-1 are used as valves for mechanical supply and exhaust smoke ventilation, the valves can also be used as smoke valves. The use of valves is carried out in accordance with regulatory requirements.
KLOP-1 dampers are not subject to installation in rooms of categories A and B due to explosion and fire hazard. In these rooms, KLOP-1 or KLOP-2 dampers are installed in an explosion-proof design.
Note: Normally open NO valves KLOP-1(60/90) can be installed both in a fire-resistant building structure (fire barrier) and outside it in a section of a fire-resistant air duct, regardless of the direction of possible thermal effects on their structures. In accordance with the requirement of paragraph 6.11 of SP 7.13130.2013, this allows the installation of dampers on either side of the fire barrier, regardless of the location of the fire in relation to this barrier. Compliance with the requirement of clause 6.11 is ensured by the presence of a casing that protects the drive of HO valves both when they are installed in a fire-resistant building structure, and when valves are installed in an air duct section outside this structure.
Valve design KLOP 1 NO and NC
KLOP-1 dampers are produced only in the "channel" type with two rectangular flanges). The valve actuator is installed outside the housing. Rectangular valve body is made of carbon cold-rolled steel with subsequent painting, round valve body is made of galvanized steel.
By special order, the body can be made of stainless steel. The body and damper of such valves are made of stainless steel (spanish “stainless steel”), the rest of the components and structural elements are made of carbon steel with anti-corrosion zinc coating.
The valve flaps are filled with thermal insulation.
Operating conditions KLP 1
Valves KLOP-1 workable in any spatial orientation.
When designing and installing valves in ventilation systems, it is recommended to take into account the convenience of access to the valve actuator and inspection hatches in its body.
When installing KLOP-1 dampers in large-section air ducts in areas located behind the place of a sharp change in the direction of the air flow, for example, behind 90° bends, it is recommended to ensure the open position of the damper damper in the plane of flow turn or to use KLOP-3 dampers.
Type of climatic modification of valves - U3 in accordance with GOST 15150-69. The dampers can be installed indoors with air temperatures from -30°C to +40°C, where fluctuations in temperature and air humidity are significantly less than outside the building.
The environment must be explosion-proof, not containing aggressive vapors and gases in concentrations that destroy metals, paintwork and electrical insulation.
Schemes of valve cassettes KLOP-1
Non-standard application of the KLOP 1 valve
The main feature of the fire damper KLOP-1 (60/90) is the possibility of using it for rooms with non-standard requirements. Fire damper KLOP-1 (60/90) can be made in several versions, for example:
- For work in conditions of high humidity
Such valves can be used on river or sea transport, fixed platforms, which is confirmed by various certificates state standard. The material of manufacture for such valves is high-quality stainless steel, and their Belimo electromechanical actuator is installed in a special shell with a high degree of protection. - To work in transport
Thanks to design features dampers KLOP-1(60/90) fire-fighting, which are intended for use in railway transport, it is possible to install them in ventilation systems and air conditioners. - For work in particularly demanding cleanliness rooms
When making KLOP-1(60) for rooms with a high sterility requirement, special stainless steel is used.
You can find out more about the features of this valve by calling us. Managers of the company Ventar-S will select you fire damper Klop-1 (60) for any purpose.
Valve options KLP 1
All KLOP-1 valves have channel type development. They are equipped with two flanges and external actuators. different types. > KLOP-1 valves with a round section can have nipple joints. Such valves are called nipple.
Normally open (NO) valves KLOP-1 are presented in several types of modifications. They can be equipped with an electromagnetic drive with a thermal lock capable of withstanding temperatures up to 72 ° C, or an electromagnetic drive without a thermal lock. Also, KLP valves can be equipped with BELIMO electromechanical actuators with thermal locking devices designed for temperatures up to 72 °C, or electromechanical actuators without such devices, and spring actuators with thermal locks that can withstand temperatures either up to 72 °С or up to 141 °С . In addition, KLOP-1 valves can be equipped with microswitches.
Normally closed (NC) and smoke dampers KLOP-1(90) and KLOP-1(60) are not equipped with thermal locks. Valves of this type, having small and medium dimensions, are equipped with an electromagnetic actuator. Large dampers KLOP-1(90) and KLOP-1(60) have BELIMO reversing actuators of the BLE or BE type or BELIMO electromechanical actuators equipped with BF or BLF return springs without TRU.
Installation of valves KLP 1
KLOP-1 valves retain their full performance when installed in any position. The design and further installation of such valves are made in accordance with calculations based on the availability of the valve for operation and accessibility to all devices that are located inside it.
KLP dampers are designed for installation indoors, where the air temperature ranges from -30 °C to +40 °C. They are installed in such a way that direct contact with natural precipitation or the formation of condensate on the valve flaps are completely excluded. If the environment surrounding the KLP valves contains aggressive vapors or gases, their concentration should not be too high. Otherwise, the aggressive environment will have a destructive effect on the metal from which the KLOP valves are made, and on the electrical insulation.
KLOP-3 dampers are designed mainly for air ducts of large cross section.
Values of coefficients of local resistance
Weight of KLOP-1 valves with BELIMO actuator
Example of ordering a valve KLOP 1
Klop-1(60)-D-EM(220)-400x400-K, Where:
(60)
- valve KLOP-1 with a fire resistance limit of 60 minutes,
D- smoke
EM(220)- with electromagnetic drive for 220 V,
400x400- with dimensions of internal section 400x400 mm,
TO- with terminal block